Our thermal insulation pipe/tube uses NBR (nitrile-butadiene rubber) as the main raw material for foaming, resulting in a fully closed-cell flexible rubber insulation material. It is manufactured without any fibrous materials such as HCHO and CFCs, which are harmful to the ozone layer. This product is suitable for the thermal insulation of various pipes and equipment operating within the temperature range of -50℃ to 110℃.
| Technical Data Specification | |||
| Property | Unit | Value | Test Method |
|---|---|---|---|
| Temperature range | °C | (-50 - 110) | GB/T 17794-1999 |
| Density range | Kg/m³ | 45-65Kg/m³ | ASTM D1667 |
| Water vapor permeability | Kg/(m.s.pa) | ≤0.91×10⁻¹³ | DIN 52 615 / BS 4370 Part 2 1973 |
| μ | - | ≥10000 | - |
| Thermal Conductivity | W/(m.k) | ≤0.030 (-20°C) | ASTM C 518 |
| ≤0.032 (0°C) | |||
| ≤0.036 (40°C) | |||
| Fire Rating | - | Class 0 & Class 1 | BS 476 Part 6 part 7 |
| Flame Spread and Smoke Developed Index | - | 25/50 | ASTM E 84 |
| Oxygen Index | - | ≥36 | GB/T 2406, ISO4589 |
| Water Absorption, % by Volume | % | 20% | ASTM C 209 |
| Dimension Stability | - | ≤5 | ASTM C534 |
| Fungi resistance | - | Good | ASTM 21 |
| Ozone resistance | Good | GB/T 7762-1987 | |
| Resistance to U.V. and weather | Good | ASTM G23 | |
Made of high-quality NBR and PVC. It is completely free from fibrous dust, benzaldehyde, and chlorofluorocarbons. Offers low heat conductivity, excellent moisture resistance, and reliable fire protection.
Widely applicable for cooling units and equipment of central air conditioning, freezing water pipes, condensing water pipes, air ducts, and hot-water pipelines.
Simple to install on new or existing pipelines. The material can be cut and glued together easily without affecting its overall thermal performance.
A large inventory is maintained to ensure reliable supplying capacity and timely shipment delivery.
Customized solutions can be offered tailored specifically to detailed project demands and customer requests.